- homeHome chevron_right
- Fire & Safety chevron_right
- Special Detectors chevron_right
- Heat‑Sensing Cables chevron_right
- Non-restorable analogs
Non‑resettable digital heat‑sensing cables (EN54-28)
Digital heat-sensitive cables for fire detection
Compatible with
Compatible with
Digital heat-sensitive cables for concealed fire hazard detection
The Thermocable ProReact EN Digital Linear Heat Detection (LHD) cable is designed using fixed-temperature technology to ensure reliable protection against overheating in high-risk applications. Ideal for tunnels, cable trays, warehouses, and escalators, this digital heat-sensitive cable enables rapid identification of temperature changes even in hard-to-access or concealed areas.
How non-resettable digital heat-sensitive cables work
The ProReact EN Digital LHD uses two twisted cores separated by a temperature-sensitive polymer. When the preset threshold is reached, the polymer softens, allowing the cores to make contact and trigger the alarm. This process is irreversible: only the activated section needs to be replaced, not the entire cable. A simple, effective, and durable solution for fire safety.
Integration and further options
arrow_back
arrow_forward
This product is available in the following versions

A1397
Control unit for DSCU-EN digital heat-sensitive cable, 2 zones

A1398
EOLU-EN end-of-line box for digital heat-sensitive cable with test function, 2-line termination

F1182
Halogen-free, low smoke heat-sensitive cable

F1192
Heat-sensitive cable in stainless steel

F1180
Halogen-free, low smoke heat-sensitive cable

F1190
Heat-sensitive cable in stainless steel

F1181
Halogen-free, low smoke heat-sensitive cable

F1191
Heat-sensitive cable in stainless steel
Technical specifications
| F1180 | F1181 | F1182 | F1190 | F1191 | F1192 | |
| Description | LHD digital cable – 78°C | LHD digital cable – 88°C | LHD digital cable – 68°C | LHD digital cable – 78°C with stainless steel braid | LHD digital cable – 88°C with stainless steel braid | LHD digital cable – 68°C with stainless steel braid |
| Type Performance EN54-28 | T078-V10-A045 | T088-V10-A065 | T068-V10-A045 | T078- V10-A045 | T088- V10-A065 | T068-V10-A045 |
| EN54-28 Environmental group | II | II | II | III | III | III |
| Nominal Activation Temperature | 78°C | 88°C | 68°C | 78°C | 88°C | 68°C |
| Max. Ambient Temperature | 45°C | 65°C | 45°C | 45°C | 65°C | 45°C |
| Minimum ambient temperature | -40°C | -40°C | -40°C | -40°C | -40°C | -40°C |
| Humidity | 0% – 98% RH | 0% – 98% RH | 0% – 98% RH | 0% – 98% RH | 0% – 98% RH | 0% – 98% RH |
| Colour | Red | Red | Red | Silver braid on red | Silver braid on red | Silver braid on red |
| Diameter | 5.72 mm ± 0.12 mm | 5.72 mm ± 0.12 mm | 5.72 mm ± 0.12 mm | 6.3 mm ± 0.12 mm | 6.3 mm ± 0.12 mm | 6.3 mm ± 0.12 mm |
| Minimum curve radius | 100 mm | 100 mm | 100 mm | 125 mm | 125 mm | 125 mm |
| Features | LSZH, UV‑resistant, oil‑resistant, flame‑retardant | LSZH, UV‑resistant, oil‑resistant, flame‑retardant | LSZH, UV‑resistant, oil‑resistant, flame‑retardant | LSZH, UV‑resistant, oil‑resistant, flame‑retardant, with mechanical and abrasion resistance | LSZH, UV‑resistant, oil‑resistant, flame‑retardant, with mechanical and abrasion resistance | LSZH, UV‑resistant, oil‑resistant, flame‑retardant, with mechanical and abrasion resistance |