- homeHome chevron_right
- Fire & Safety chevron_right
- Emergency Lighting chevron_right
- HARPER MANAGER
Harper Manager
Central unit for lighting system


Intelligent supervision for plant safety
Harper Manager is the supervisory control panel that simplifies the control of lighting and emergency signaling systems, managing up to 8 loops and 240 devices. It collects and stores all information from the lamps, ensuring complete and constant monitoring.
Advanced management and automated maintenance
With Harper Manager and Harper Manager XL, you can perform function and autonomy tests, adjust brightness, enable or disable emergency mode, and manage the switching on of permanent fixtures (SA). An innovative solution that streamlines periodic maintenance and reduces the risk of malfunction.

This product is available in the following versions

HPMNG
Harper Manager central unit with a 2-Loop module included
Technical specifications
HPMNG | |
Installation | Wall-mounted and 19" rack-mounted |
Power supply voltage | 220/230 Vac, 50-60 Hz |
Current draw | 20 VA |
Battery | 2 x Pb 12V 7 Ah |
Insulation class | I |
Additional information | Manages up to 8 loops and up to 240 devices on each loop Manages up to 80 logical groups |
Maximum loop length | 2000 m (with twisted and shielded cable) |
IP rating | IP30 |
Compliant with regulations | UNI 11222, EN 50172 |
Dimensions (HxWxD) | 351 x 406 x 181 mm |
Other similar products